The positioner links the DCS and valve: it reads the command, measures actual position and adjusts air to bring the actuator to the setpoint. Geyser IC supports both EDP300 and the widely installed TZIDC V18345.
4–20 mA/HART, auto-adjustment, local operation, linear or rotary actuators, remote sensing and robust construction. ABB positions it as a standard-performance family and continues to offer it.
Lifecycle to be checked by codeOlder V18346/V18347 fieldbus variants have had different lifecycle statuses. We check current ABB availability for each new quotation.
AV1 / AV2 / AVPT
AV1 and AV2 are conventional positioners: AV1 uses pneumatic input, AV2 electrical 4–20 mA input. AVPT is a position transmitter with a 4–20 mA output and separate documentation.
HW 5.01 generation datasheet. Check hardware revision and nameplate options. The manual distinguishes versions with and without non-contact position sensing.
TZIDC is the established standard-performance platform still offered by ABB. EDP300 is the advanced choice for more extensive diagnostics, high air capacity, optional modules, pressure sensors or demanding applications.
Is TZIDC V18345 still current?
Yes. ABB continues to list TZIDC as a current 4–20 mA/HART product. Availability of individual variants and codes must still be checked.
What is the difference between V18345 and V18348?
V18345 identifies standard HART TZIDC; V18348 identifies TZIDC-200 with a flameproof enclosure. V18349 and V18350 are flameproof fieldbus variants.
What do auto-adjustment and adaptation do?
Auto-adjustment identifies stroke and initial parameters; adaptation optimises control behaviour. Neither replaces correct mechanical mounting.
When is a remote sensor needed?
Where the positioner must be separated from vibration, heat, poor access or harsh conditions, leaving only the position sensor at the valve stem.
Does a positioner always solve stiction?
No. It can partly compensate for deadband and friction, but overtight packing, an undersized actuator or faulty mechanics require work on the valve itself.
I/P converter or positioner?
An I/P converts the signal without knowing valve position. A positioner uses position feedback to correct actuator air in a closed loop.