Electromagnetic
ProcessMaster, WaterMaster, AquaMaster4, HygienicMaster and AquaProbe.
Explore electromagnetic metersThere is no single best flowmeter. Selection depends on the fluid, phase, conductivity, accuracy, pressure loss, nominal size, available straight runs and measurement objective. Start with the process requirements to find the most suitable technology.
| Typical application | First technology to consider | Why | Points to check |
|---|---|---|---|
| Water, wastewater and conductive slurries | Electromagnetic | Economical, with no moving parts or significant pipe restriction. | Requires sufficient conductivity and a full pipe. |
| Saturated or superheated steam, wet gases | Vortex / Swirl | Robust, without moving parts, and well suited to utilities and energy applications. | Size for the actual range. Vortex requires longer straight runs; Swirl needs much less space. |
| Dry gases, compressed air and industrial gases | Thermal mass | Direct mass flow and excellent low-flow sensitivity. | Gas composition, deposits, condensation and flow profile affect measurement. |
| High accuracy, batching, density or concentration | Coriolis | Direct mass flow, density and temperature, with high repeatability. | Cost and pressure loss may be higher, especially at large diameters. |
| Retrofits without cutting the pipe / meter checks | Clamp-on ultrasonic | No fluid contact and no shutdown required for installation. | Pipe condition, liners, bubbles, solids and acoustic coupling are critical. |
| Large diameters / DP project specifications | Orifice / TORBAR / Pitot | Standardised technology, readily integrated with DP transmitters. | Orifice: pressure loss. Pitot: installation and alignment are critical. |
| Simple local indication and low flow rates | Variable area | No power supply, low cost and an immediate reading. | The scale depends on the fluid and reference pressure and temperature, especially for gases. |

ProcessMaster, WaterMaster, AquaMaster4, HygienicMaster and AquaProbe.
Explore electromagnetic meters
Liquids, gases and especially steam; Swirl for compact installations.
Explore Vortex / Swirl
Direct mass flow, density and temperature when accuracy and repeatability are priorities.
Explore Coriolis meters
Dry gases, compressed air, utilities and low flow rates.
Explore thermal mass meters
Multibrand inline or clamp-on meters for retrofits and non-invasive checks.
Explore ultrasonic meters
Orifices, TORBAR, Pitot probes, nozzles and Venturi tubes with differential pressure transmitters.
Explore DP primary elements
Rotameters and purge meters for local indication and low flow rates.
Explore variable area metersFor many technologies, selecting solely by existing pipe size leads to oversized instruments and poor low-flow resolution. Send minimum, normal and maximum flow rates: we assess the operating range before selecting the meter size.